RMSX series bus duct are applied to the power supply and distribution system of AC three-phase-four-wire, three-phase-five-wire,50-60Hz, rated voltage 660V and rated operational current 2500-4000A, to assume the task of distribution. It`s suitable for load connection of low-voltage distribution board and big, middle-size, as connection of high current to transmission and used for power transformer, low-voltage distribution board and heavy load. RMSX are mainly used for electric welding, industrial furnace, factory, high-rise building and others of power station, electric manufacturing.
1. suit for large span installation
2. convenience installation
3. safe and reliable structure,
4. flexible wiring,
5. strong inter change ability.
RMSX series bus duct are applied to the power supply and distribution system of AC three-phase.four-wire, three- phase-five-wire, 50-60Hz, rated voltage 660V and rated operational current2500~4000A, to assume the task of distribution. lt’s suitable for load connection of low-voltagedistribution board and big, middle-size, as connection of high current to transmission and used foipower transformer, low-voltage distribution board and heavy load. RMSX are mainly used foielectric weiding, industria furnace, factorv, hiah-rise building and others of power station, electricmanufacturing.
RMSX series sealed bus duct are mainly made up by nameplate. hiah strenath case. copper bar anobus bar, support insulator, PVC heat-shrinkable tubing, F4 regular basis and other components. Busduct by different current standard, transfer all need use low-voltage transfer type distribution boxacting on connect (transfer) and others with related power of low-voltage distribution system.The series bus duct is suit for large span installation, convenience installation, safe and reliablestructure, flexible wiring, strong inter change abilitv and other characteristic.
Customized products, please consult the salesman for details
The specifications of the cable as Table 2-2 | ||||
Model | Number of Cores | Rated voltage (kV) | ||
0.6/1 | 1.8/3 | 3.6/6、6/6、6/10 | ||
Nominal cross-sectional area (mm2) | ||||
MVV | 3 | 1.5~300 | 10~300 | 10~300 |
MVV22 | 3 | 2.5~300 | 10~300 | 10~300 |
MVV32 | 3 | - | - | 16~300 |
MVV42 | 3 | - | - | 16~300 |
MVV | 3+1 | 4~300 | 10~300 | - |
MVV22 | 3+1 | 4~300 | 10~300 | - |
MVV | 4 | 4~185 | 4~185 | - |
MVV22 | 4 | 4~185 | 4~185 | - |
Structure
Straightway
Standard length for straightway unit is 3m,6m,9m,meetthe workshop long-span installation,can design socketin any position as needed,minimum spacing for socketsare noless than 0.5m.
Plate grafting unit
RMSX bus jack box can design two kinds box: steel case and whole resin case, the maximum currentup to 630A, components are installed into box can handpick as user needed.
Inlet wire unit
Generally, inlet wire unit was used for the top position of bus duct, convenient for bus duct toconnecting with cable and distribution cabinet. lt can join up any size cable, the top inlet line box isdivided into three ways to outlet, cable in outlet line position with protection tube.
RMSX COPPER BUS
Rated current |
3-line | 4-line | 5-line | ||||||
W(mm) | H(mm) | Weight(kg/m) | W(mm) | H(mm) | Weight(kg/m) | W(mm) | H(mm) | Weight(kg/m) | |
250 | 159 | 91 | 17 | 159 | 91 | 19 | 159 | 91 | 21 |
400 | 159 | 101 | 19 | 159 | 101 | 21.5 | 159 | 101 | 24 |
630 | 159 | 111 | 21 | 159 | 111 | 24 | 159 | 111 | 27 |
800 | 159 | 126 | 24 | 159 | 126 | 28 | 159 | 126 | 31.5 |
1000 | 159 | 141 | 26.5 | 159 | 141 | 32 | 159 | 141 | 35.5 |
1250 | 159 | 176 | 33.5 | 159 | 176 | 42 | 159 | 176 | 46 |
1600 | 159 | 196 | 41.5 | 159 | 196 | 45 | 159 | 196 | 59 |
2000 | 154 | 136 | 74 | 234 | 136 | 76 | 234 | 136 | 84 |
2500 | 154 | 165 | 75 | 234 | 165 | 90 | 234 | 165 | 88 |
3150 | 154 | 201 | 85 | 234 | 201 | 107 | 234 | 201 | 120 |
VARIOUS BENDING UNIT
Bending unit have L type, Z type, Z type, T type and Cross type, used for connecting for horizontaand verticality distribution bus duct and change the direction of bus duct.
Main line rated current (A) | 100-250 | 3150-3500 | 4000-5000 | |
L1 | 500mm | 650mm | 800mm | |
L2 | ||||
L3 | ||||
L4 |
Reversing Unit
RMSX bus duct provided L type,T type, Z type anddeformed bend type are designed by standard,canconvenient to change the movement of bus duct systemto adapt complicated site condition. At the same time.nave small outline size,good appearance and savespace foruser. | ||||||||||
Standard size: | ||||||||||
L-type:500×500 | ||||||||||
T-type:500 x500 x500 | ||||||||||
Z-type:500x300x500 | ||||||||||
Deformed bend Type: 500 x 500 x 500 x500 |
Reducing unit
Reducing unit is used for connect different ratedcurrent branch line unit filter section. Standardlength for reducing unit is 1m,can from anycurrent step to another current level of 100A5000A
Expansion unit
Expansion unit is used for absorbing bus branchline change of bus duct axial variation produceoby thermal expansion. General, installationlength for bus duct is more than 80m and mustadd a section in place.
RMSX series bus duct are applied to the power supply and distribution system of AC three-phase.four-wire, three- phase-five-wire, 50-60Hz, rated voltage 660V and rated operational current2500~4000A, to assume the task of distribution. lt’s suitable for load connection of low-voltagedistribution board and big, middle-size, as connection of high current to transmission and used foipower transformer, low-voltage distribution board and heavy load. RMSX are mainly used foielectric weiding, industria furnace, factorv, hiah-rise building and others of power station, electricmanufacturing.
RMSX series sealed bus duct are mainly made up by nameplate. hiah strenath case. copper bar anobus bar, support insulator, PVC heat-shrinkable tubing, F4 regular basis and other components. Busduct by different current standard, transfer all need use low-voltage transfer type distribution boxacting on connect (transfer) and others with related power of low-voltage distribution system.The series bus duct is suit for large span installation, convenience installation, safe and reliablestructure, flexible wiring, strong inter change abilitv and other characteristic.
Customized products, please consult the salesman for details
The specifications of the cable as Table 2-2 | ||||
Model | Number of Cores | Rated voltage (kV) | ||
0.6/1 | 1.8/3 | 3.6/6、6/6、6/10 | ||
Nominal cross-sectional area (mm2) | ||||
MVV | 3 | 1.5~300 | 10~300 | 10~300 |
MVV22 | 3 | 2.5~300 | 10~300 | 10~300 |
MVV32 | 3 | - | - | 16~300 |
MVV42 | 3 | - | - | 16~300 |
MVV | 3+1 | 4~300 | 10~300 | - |
MVV22 | 3+1 | 4~300 | 10~300 | - |
MVV | 4 | 4~185 | 4~185 | - |
MVV22 | 4 | 4~185 | 4~185 | - |
Structure
Straightway
Standard length for straightway unit is 3m,6m,9m,meetthe workshop long-span installation,can design socketin any position as needed,minimum spacing for socketsare noless than 0.5m.
Plate grafting unit
RMSX bus jack box can design two kinds box: steel case and whole resin case, the maximum currentup to 630A, components are installed into box can handpick as user needed.
Inlet wire unit
Generally, inlet wire unit was used for the top position of bus duct, convenient for bus duct toconnecting with cable and distribution cabinet. lt can join up any size cable, the top inlet line box isdivided into three ways to outlet, cable in outlet line position with protection tube.
RMSX COPPER BUS
Rated current |
3-line | 4-line | 5-line | ||||||
W(mm) | H(mm) | Weight(kg/m) | W(mm) | H(mm) | Weight(kg/m) | W(mm) | H(mm) | Weight(kg/m) | |
250 | 159 | 91 | 17 | 159 | 91 | 19 | 159 | 91 | 21 |
400 | 159 | 101 | 19 | 159 | 101 | 21.5 | 159 | 101 | 24 |
630 | 159 | 111 | 21 | 159 | 111 | 24 | 159 | 111 | 27 |
800 | 159 | 126 | 24 | 159 | 126 | 28 | 159 | 126 | 31.5 |
1000 | 159 | 141 | 26.5 | 159 | 141 | 32 | 159 | 141 | 35.5 |
1250 | 159 | 176 | 33.5 | 159 | 176 | 42 | 159 | 176 | 46 |
1600 | 159 | 196 | 41.5 | 159 | 196 | 45 | 159 | 196 | 59 |
2000 | 154 | 136 | 74 | 234 | 136 | 76 | 234 | 136 | 84 |
2500 | 154 | 165 | 75 | 234 | 165 | 90 | 234 | 165 | 88 |
3150 | 154 | 201 | 85 | 234 | 201 | 107 | 234 | 201 | 120 |
VARIOUS BENDING UNIT
Bending unit have L type, Z type, Z type, T type and Cross type, used for connecting for horizontaand verticality distribution bus duct and change the direction of bus duct.
Main line rated current (A) | 100-250 | 3150-3500 | 4000-5000 | |
L1 | 500mm | 650mm | 800mm | |
L2 | ||||
L3 | ||||
L4 |
Reversing Unit
RMSX bus duct provided L type,T type, Z type anddeformed bend type are designed by standard,canconvenient to change the movement of bus duct systemto adapt complicated site condition. At the same time.nave small outline size,good appearance and savespace foruser. | ||||||||||
Standard size: | ||||||||||
L-type:500×500 | ||||||||||
T-type:500 x500 x500 | ||||||||||
Z-type:500x300x500 | ||||||||||
Deformed bend Type: 500 x 500 x 500 x500 |
Reducing unit
Reducing unit is used for connect different ratedcurrent branch line unit filter section. Standardlength for reducing unit is 1m,can from anycurrent step to another current level of 100A5000A
Expansion unit
Expansion unit is used for absorbing bus branchline change of bus duct axial variation produceoby thermal expansion. General, installationlength for bus duct is more than 80m and mustadd a section in place.